Schneider 140CPU11303 Seven common problems of the CPU module

  • Schneider 140CPU11303 FAQs

Schneider 140CPU11303

Question 1:Is it easy to report insufficient memory when using IEC programming for 140CPU11303?

Solution:140CPU11303 corresponds to two firmware:one corresponds to 140CPU11303,and one corresponds to 140CPU11303S.When the corresponding 140CPU11,303 firmware is used,the CPU supports both LL984 and IEC,but the IEC capacity will be small.If you are sure that your application is entirely IEC application,please update the CPU firmware to 140CPU11303S firmware.After this operation,the CPU IEC programming capacity will be greatly expanded.Specific operations:The Quantum 11303 firmware is updated to support only IEC programming;In Concept software,change the CPU model from 140CPU11303 to 140CPU11303S.

Problem 2:Brush the 140CPU11303 PV06 firmware to 140CPU11303S,download the program,and it runs normally,but power is supplied again after power failure.The Run light is off,and the IO module Active light is off.The CPU cannot be started,and an error 0004 is reported.After downloading the program again,it is OK

Solution:The 140CPU11303 firmware is updated to 140CPU11303S,the program is downloaded,the CPU is started and running normally,and the CPU is powered back after power failure.The normal situation is what state the CPU was in before power failure and what state it is still in after power failure.The phenomenon described in the title is obviously abnormal.We perform the same operation on another new 140CPU11303 PV06 CPU as described in the title,The fault phenomenon described in the title is not reproduced,and it is judged that the fault phenomenon is an individual fault rather than a batch fault.It has nothing to do with the upgrade of the 140CPU11303 hardware version to PV06 and the firmware update file bug corresponding to PV06.In addition,when the CPU is shut down,the Active light on all IO modules is off,which is a normal phenomenon.

Problem 3:140CPU11303 reported an error when downloading the program,and the displayed error code is"OLI-21707".However,if only the configuration is changed,other programs remain unchanged,and then downloaded to 140CPU43412A,everything is normal

Solution:The reason for the above error is that the user programmed Project contains EFBs involving floating point operations.For 140CPU43412A,it can support floating point operations without any processing.For 140CPU11303,if it does not do any processing,it does not support floating point operations.Therefore,if the corresponding loadable file is not downloaded before the program is downloaded,an error will always be reported when downloading the project to 140CPU11303,However,when downloaded to 140CPU43412A,everything will be normal The solution is to download the loadable file named"EMUQ"before downloading the program.

Problem 4:The power supply of the 140CPU11303 device is restored after power failure,and the CPU cannot start automatically.How to solve this problem

Solution:After the 140CPU11303 equipment is powered off,the CPU will be restored to the state before the equipment is powered off,and the 140CPU43412A/53414A cannot be configured with software to restore the state after the equipment is powered on.If the CPU state is run before the power failure and stop after the power supply is restored,it is highly suspected that the device failure will cause the CPU to fail to start.

Question 5:What are the functions of ASCII/RTU/MEM dial codes on the front panel of Concept Quantum CPU

www.plc-module.com

resolvent:

The setting of relevant parameters of 140CPU11303 MB is based on the setting position of the"Modbus"setting switch on the CPU module,as shown in the following figure:

Modbus

If the"Modbus"setting switch is set to the"ASCII"position,the parameter Settings are as follows:

Modbus

If the"Modbus"setting switch is set to the"RTU"position,the parameter Settings are as follows:

If the Modbus Settings switch is set to the MEM position,the parameters are set as follows:

Q6:When the Quantum series CPU is powered down,what is the maximum storage period of memory data through the battery?

140CPU11302   454 days

140CPU11303   238 days

140CPU43412X 238 days

140CPU53414X 119 days

Q7:What are the main frequencies of Quantum and Premium processors?

Quantum Series:

CPU ModelProcessor Main Frequency
140CPU3111066MHZ
140CPU43412U66MHZ
140CPU65150166MHZ
140CPU65160266MHZ
140CPU65260266MHZ
140CPU67060266MHZ
140CPU67160266MHZ
140CPU67260266MHZ
140CPU67261266MHZ
140CPU1130220MHZ
140CPU1130320MHZ
140CPU43412A66MHZ
140CPU53414B133MHZ

Premium Series:

Unity ProcessorMain ProcessorMain processor frequency (HZ)Automatic processorAutomatic processor frequency (HZ)
TSX P57 CA0244MINTEL  AMD 48648SONIX48
TSX P57 CD0244MINTEL  AMD 48848SONIX48
TSX PCI57 204MINTEL  AMD 48672SONIX48
TSX PCI57 354MINTEL  AMD 48672SONIX48
TSX P57 0244MINTEL  AMD 48640SONIX48
TSX P57 104MINTEL  AMD 48648SONIX48
TSX P57 1634MINTEL  AMD 48648SONIX48
TSX P57 154MINTEL  AMD 48848SONIX48
TSX P57 204MINTEL  AMD 48612SONIX48
TSX P57 2634MINTEL  AMD 48672SONIX48
TSX P57 254MINTEL  AMD 48672SONIX48
TSX P57 304MINTEL  AMD 48612SONIX48
TSX P57 9834MINTEL  AMD 48672SONIX48
TSX P57 364MINTEL  AMD 48672SONIX48
TSX P57 4834MINTEL PENTIUM 166/266 MMX166PHOENIX66
TSX P57 454MINTEL PENTIUM 166/266 MMX166PHOENIX66
TSX P57 5634MINTEL PENTIUM 166/266 MMX166PHOENIX66
TSX P57 654MINTEL PENTIUM 166/266 MMX166PHOENIX66
TSX P57 6634MINTEL PENTIUM 166/266 MMX166PHOENIX66
TSX H57 24MINTEL PENTIUM 166/266 MMX166PHOENIX66
TSX H57 44MINTEL PENTIUM 166/266 MMX166PHOENIX66

Related CPU modules:

SCHNEIDER 140CPU67160

image.png

SCHNEIDER140CPU67060

image.png

Share:

More Posts

RELIANCE

RELIANCE Reliance Standard Life Insurance Company is a leading provider of financial protection, absence management and supplemental health benefits solutions, driven by technology and an integrated customer experience. We distribute these solutions through independent brokers and agents to employer groups of all sizes. Reliance Standard strives to save employers time and create efficiencies when planning

ABB

ABB is a global leader in power and automation technology. It is committed to providing solutions to customers in industry, energy, power, transportation and construction industries, helping customers improve production efficiency and energy efficiency, and reducing adverse impacts on the environment. ABB Group's business covers more than 100 countries around the world.   We supply

Send Us A Message