PRODUCTS CATEGORY
Menu
HOT PRODUCT
Contact Us
- josephine@seeiyo.com
-
Wechat,Telegram,Line,
Whatsapp:+8618030983224 - Skype:1004611300@qq.com
Sale!
Siemens 6ES7322-1BL00-0AA0
Total current of the outputs (per group)horizontal installation— up to 40 °C, max.4 A— up to 60 °C, max.3 Avertical installation— up to 40 °C, max.2 ACable length
- shielded, max.
- unshielded, max.
- Diagnostic alarm
- Diagnostic information readable
- Wire-break
- Short-circuit
- missing load voltage
- Rated load voltage PWR (green)
- Fuse OK FSG (green)
- Group error SF (red)
- Status indicator digital output (green)
- Channel fault indicator F (red)
- between the channels
- between the channels, in groups of
- between the channels and backplane bus
Description
SIMATIC S7-300, Digital output SM 322, isolated, 32 DO, 24 V DC, 0.5A, 1x 40-pole, Total current 4 A/group (16 A/module)
Load voltage L+
- Rated value (DC)
24 V
- permissible range, lower limit (DC)
20.4 V
- permissible range, upper limit (DC)
28.8 V
Input current
from load voltage L+ (without load), max.
160 mA
from backplane bus 5 V DC, max.
110 mA
Power loss
Power loss, typ.
6.6 W
Digital outputs
Number of digital outputs
32
Short-circuit protection
Yes; Electronic
- Response threshold, typ.
1 A
Limitation of inductive shutdown voltage to
L+ (-53 V)
Controlling a digital input
Yes
Switching capacity of the outputs
- on lamp load, max.
5 W
Load resistance range
- lower limit
48 Ω
- upper limit
4 kΩ
Output voltage
- for signal "1", min.
L+ (-0.8 V)
Output current
- for signal "1" rated value
0.5 A
- for signal "1" permissible range for 0 to 40 °C, min.
5 mA
- for signal "1" permissible range for 0 to 40 °C, max.
0.6 A
- for signal "1" permissible range for 40 to 60 °C, min.
5 mA
- for signal "1" permissible range for 40 to 60 °C, max.
0.6 A
- for signal "1" minimum load current
5 mA
- for signal "0" residual current, max.
0.5 mA
Output delay with resistive load
- "0" to "1", max.
100 µs
- "1" to "0", max.
500 µs
Parallel switching of two outputs
- for uprating
No
- for redundant control of a load
Yes; only outputs of the same group
Switching frequency