Sichuan Seeiyo Technology CO.,Ltd
Sale!

Siemens 6ES7322-1BL00-0AA0

Total current of the outputs (per group)horizontal installation— up to 40 °C, max.4 A— up to 60 °C, max.3 Avertical installation— up to 40 °C, max.2 ACable length
  • shielded, max.
1 000 m
  • unshielded, max.
600 mInterrupts/diagnostics/status information AlarmsNoDiagnostics functionNoAlarms
  • Diagnostic alarm
NoDiagnoses
  • Diagnostic information readable
No
  • Wire-break
No
  • Short-circuit
No
  • missing load voltage
NoDiagnostics indication LED
  • Rated load voltage PWR (green)
No
  • Fuse OK FSG (green)
No
  • Group error SF (red)
No
  • Status indicator digital output (green)
Yes; per channel
  • Channel fault indicator F (red)
NoPotential separation Potential separation digital outputs
  • between the channels
Yes
  • between the channels, in groups of
8
  • between the channels and backplane bus
Yes; OptocouplerIsolation Isolation tested with500 V DCconnection method required front connector40-pinDimensions Width40 mmHeight125 mmDepth120 mmWeights Weight, approx.260 g

Description

SIMATIC S7-300, Digital output SM 322, isolated, 32 DO, 24 V DC, 0.5A, 1x 40-pole, Total current 4 A/group (16 A/module)

Load voltage L+

  • Rated value (DC)

24 V

  • permissible range, lower limit (DC)

20.4 V

  • permissible range, upper limit (DC)

28.8 V

Input current

from load voltage L+ (without load), max.

160 mA

from backplane bus 5 V DC, max.

110 mA

Power loss

Power loss, typ.

6.6 W

Digital outputs

Number of digital outputs

32

Short-circuit protection

Yes; Electronic

  • Response threshold, typ.

1 A

Limitation of inductive shutdown voltage to

L+ (-53 V)

Controlling a digital input

Yes

Switching capacity of the outputs

  • on lamp load, max.

5 W

Load resistance range

  • lower limit

48 Ω

  • upper limit

4 kΩ

Output voltage

  • for signal "1", min.

L+ (-0.8 V)

Output current

  • for signal "1" rated value

0.5 A

  • for signal "1" permissible range for 0 to 40 °C, min.

5 mA

  • for signal "1" permissible range for 0 to 40 °C, max.

0.6 A

  • for signal "1" permissible range for 40 to 60 °C, min.

5 mA

  • for signal "1" permissible range for 40 to 60 °C, max.

0.6 A

  • for signal "1" minimum load current

5 mA

  • for signal "0" residual current, max.

0.5 mA

Output delay with resistive load

  • "0" to "1", max.

100 µs

  • "1" to "0", max.

500 µs

Parallel switching of two outputs

  • for uprating

No

  • for redundant control of a load

Yes; only outputs of the same group

Switching frequency

 

Enquiry

=